Home > Electrical Supply > Marine Battery Charger > DC/DC Battery Chargers >

Anaylytic 100A, 12V Out, 20-35V In, Isolated DC/DC Battery Charger, 2 Bank, 19" Rack Mount, BCD1315R-24-12
Anaylytic 100A, 12V Out, 20-35V In, Isolated DC/DC Battery Charger, 2 Bank, 19" Rack Mount, BCD1315R-24-12


 
List Price: US$2,197.00
Our Price: US$2,099.00
You save US$98.00!



Availability:: Usually ships the next business day
Product Code: BCD315R-24-12

Description
 

BCD1315R DC Battery Charger

BENEFITS
  • Efficient and Accurate Battery Charging
  • No Interference with radios or other sensitive electronics
  • Ideal for unattended operation with dry contact output fail relay and automatic recovery from most faults
  • Conservative design ensures years of safe and trouble free operation

Download BC1315R Datasheet

The BCD1315R Rack mount DC Source Battery Charger charges a 12V, 24V or 48V one or two bank battery system (batteries must share a common ground) from a 24 or 48 VDC source.

The newly updated Current Mode switching design offers 60% more power in the same 2U rackmount enclosure as our BCD1015R series. The low ripple charging profile and standard equalize cycle greatly increases the lifetime of expensive battery systems. Extra input and output filtering reduce EMI to extremely low levels. Reliability features include an input fuse, thermal shutdown, current limiting, reverse battery hookup protection and output short circuit protection with automatic recovery.

The output voltage is easily adjusted above or below the standard output voltage to accommodate special charging requirements. A high quality bright LED Digital Volt/Ammeter allows the monitoring of charging current and charging voltage. We are confident that you will get many years of reliable service from this DC Battery Charger.

Features

  • Fully Isolated Design
  • Adjustable output voltage for charging standard or deep cycle lead-acid, VRLA or Gel cell type battery
  • User selectable 2 or 3 stage charging profile/li>
  • Battery temperature compensation
  • Battery overheat detection and shutdown with automatic recovery (using supplied battery temperature sensor)
  • Extremely rugged and well suited for demanding environments
  • Ultra-quiet low EMI operation
  • Can be left permanently connected
  • Spark free connection to batteries
  • Battery reverse polarity connection protected
  • Audible & visual indicators for output overload, low input voltage, low output voltage & over-temperature
  • Over-temperature shutdown with automatic recovery
  • Short circuit protection with automatic recovery
  • Output over-voltage crowbar
  • Dry contact output fail relay
  • 3 year parts and labour warranty

Applications

  • Telecom Central Offices
  • Electric Utilities and Substations
  • Marine & other rugged environments
  • Manufacturing Plants
  • Steel Mills
  • Military Applications (COTS)
  • Industrial Controls
  • Railway trackside cabinets
Electrical [Input]
Nominal Vac (Ip) 24 48
Actual (VDC) 20-35V 40-60V
Input Amps (Max) 80A 40A
Input Fuse (ATC) 40A x 3 20 x 3
Noise on Input <100mV <50mV
Electrical [Output]
Output Nominal 12V (1 Bank) 24 (1 or 2 Bank) 48 (1 or 2 Bank)
Stages 2 (constant current to float) or 3 (constant current to absorption to float) - user selectable
Float Voltage (VDC) 13.6 27.2 54.4
Absorption Voltage (VDC) 14.4 28.8 57.6
Voltage Adjustment Range (VDC) +/- 1V +/- 2V +/- 4V
Temperature Compensation -30mV/°C -60mV/°C -1200mV/°C
Charging Current (Amps) 100A 50A 25A
Absorption to Float Current (Amps) 10 5.0 2.5
Battery Size
(Amp Hrs.)
200-400 100-200 50-100
Output Overvoltage Crowbar Trip Voltage 16V 32V 64V
Output Ripple & Noise < 50 mV
Regulation
(Line & Load)
< +/- 0.5%
Duty Cycle Continious 100% for 24hrs per day
Efficiency > 83% @ Maximum Output
Stages 2 or 3 (user selectable)
Environmental Specification
Operating Temp. Range -25° to +40°C @ maximum output
Derate Linearly 2.5% per°C from +40°C to +80°C
(Optional -40°C extra wide temp. operation avail.)
Humidity 0 - 95% Relative Humidity(non-condensing)
Audible Noise NONE - 34.5 dB at 1 meter when fan operating, 0 dB otherwise
Typical Service Life >10 years (87,600 hours)
Isolation Input-Case & Input-Output 1500VDC (500V @ 24V I/P)
Output-Case 500VDC (1500VDC @ 48V O/P)
Mechanical Specification
Depth 13.5 in/ 34.3 cm
Width 19.0 in/ 48.3 cm
Height 2u(3.5 in)/ 8.9 cm
Clearance 1 inch (2.5 cm) all around
Material Marine Grade Aluminium
Finish Black Anodize / Powder Epoxy Coat
Fastenings All 18-8 Stainless Steel
Weight 12.0 lb / 5.5 kg
Connections Four contact output terminals
Warranty 3 years
Safety Designed to meet CSA 22.2.107.1 & UL458 
Note: The price is subject to change at any time without any notice. Not responsible for any typographical errors. Any products can be cancelled from sale at any time.